Illustration
![](https://bepis.pl/wp-content/uploads/2015/02/Wymienniki-Ciepła-Pojemnościowe-typ-WP-6_6.jpg)
Gallery
Description
Application
Capacity heat exchangers are designed for heating water for communal and industrial purposes. They may work at heating medium pressure 0,6 MPa and heated medium pressure 0,6 MPa, and at tank temperature up to 1000 C, coil pipe up to 2000 C.
Construction
Capacity heat exchangers are made of structural carbon steel. The a/m exchangers are coated with anti-corrosion primer on the outside and with magnesium protector on the inside.
As a standard, heat exchangers are not equipped with thermal insulation.
Designation example
CAPACITY HEAT EXCHANGER, TYPE WP 6/6-9/I
Number 6 / 6 – represents max. pressure of heated/heating medium in bars.
Number 9 – represents number of the exchanger.
Number I – represents number of the coil pipe.
TABLE DIMENSIONS OF TERMAL EFFICIENCY
CALCULATION 1KW=860 KCAL/H
Type | Capacity min water tank Vn | Capacity heating system
V`grz |
Diameter tank
Dw |
Coil | Lenght total
L |
Lenght tank L1 | Diameter heads D1 | Diameter tubes | Intial Temp. wather Two= +50C | Weight | ||||||||||
No coil | Heaiting surfaces | Weight coil without protector | AA1 | BB1 | øE | O |
The vapor pressure and temperature.
|
The parameters of heating water | ||||||||||||
0,5bar110,8°C | 3bar142,9°C | 6bar164,2°C | 90/70 | 130/70 | 150/70 | |||||||||||||||
dm3 | D | mm | – | m2 | kg | mm | mm | mm | kW | kW | kW | kW | kW | kW | ~kg | |||||
BWP-6/6- 250/600/10 | 250 | 10 | 600 | I | 0,5 | 19 | 1293 | 1020 | 273 | 1 ¼” | 1 ¼” | 40 | ¾” | 38,2 | 53,1 | 62,9 | 12,8 | 15,1 | 16,3 | 133 |
BWP-6/6- 250/600/11 | 11 | II | 0,7 | 22 | 53,6 | 74,4 | 88,0 | 17,4 | 19,8 | 20,9 | 138 | |||||||||
BWP-6/6- 400/600/11 | 400 | 11 | 600 | I | 0,8 | 25 | 1943 | 1670 | 273 | 1 ¼” | 1 ¼” | 40 | ¾” | 61,3 | 85,0 | 100,6 | 22,1 | 29,1 | 31,4 | 192 |
BWP-6/6- 400/600/13 | 13 | II | 1,2 | 29 | 91,9 | 127,6 | 150,8 | 33,7 | 43,0 | 47,7 | 197 | |||||||||
BWP-6/6- 630/700/13 | 630 | 13 | 700 | I | 1,3 | 31 | 2248 | 1975 | 273 | 1 ¼” | 1 ¼” | 40 | ¾” | 91,9 | 127,6 | 150,8 | 33,7 | 73,0 | 47,7 | 292 |
BWP-6/6- 630/700/16 | 16 | II | 2,2 | 43 | 166,9 | 231,8 | 274,1 | 61,6 | 80,2 | 87,2 | 304 | |||||||||
BWP-6/6- 1000/900/42 | 1000 | 42 | 900 | I | 1,8 | 60 | 2323 | 1947 | 406 | 80 | 65 | 50 | 1 ½” | 137,8 | 191,3 | 226,3 | 51,2 | 66,3 | 73,3 | 379 |
BWP-6/6- 1000/900/48 | 48 | II | 2,7 | 71 | 206,6 | 287,0 | 339,5 | 76,8 | 100,0 | 110,5 | 391 | |||||||||
BWP-6/6- 1250/900/44 | 1250 | 44 | 900 | I | 2,2 | 67 | 2753 | 2377 | 406 | 80 | 65 | 50 | 1 ½” | 168,4 | 233,9 | 276,6 | 64,0 | 84,9 | 95,4 | 427 |
BWP-6/6- 1250/900/49 | 49 | II | 3,3 | 86 | 252,6 | 350,9 | 415,0 | 96,5 | 127,9 | 141,9 | 446 | |||||||||
BWP-6/6- 1500/1000/48 | 1500 | 48 | 1000 | I | 2,6 | 72 | 2650 | 2274 | 406 | 80 | 65 | 50 | 1 ½” | 199,1 | 276,4 | 326,9 | 75,6 | 100,0 | 110,5 | 454 |
BWP-6/6- 1500/1000/51 | 51 | II | 4,7 | 100 | 359,8 | 499,7 | 590,9 | 137,2 | 181,4 | 200,0 | 492 | |||||||||
BWP-6/6- 2000/1250/49 | 2000 | 49 | 1250 | I | 3,36 | 83 | 2400 | 2188 | 406 | 80 | 65 | 50 | 1 ½” | 257,2 | 357,3 | 422,4 | 96,5 | 126,8 | 140,7 | 622 |
BWP-6/6- 2000/1250/52 | 52 | II | 6,76 | 114 | 440,2 | 611,3 | 722,9 | 166,3 | 217,5 | 239,6 | 654 | |||||||||
BWP-6/6- 2500/1250/51 | 2500 | 51 | 1250 | I | 4,3 | 94 | 2800 | 2834 | 406 | 80 | 65 | 50 | 1 ½” | 329,2 | 457,2 | 540,7 | 127,9 | 171,0 | 190,7 | 719 |
BWP-6/6- 2500/1250/62 | 62 | II | 7,1 | 133 | 543,6 | 754,9 | 892,7 | 211,7 | 283,8 | 315,2 | 757 | |||||||||
BWP-6/6- 3150/1250/57 | 3150 | 57 | 1250 | I | 5,5 | 110 | 3365 | 2990 | 406 | 80 | 65 | 50 | 1 ½” | 421,1 | 584,8 | 691,5 | 167,5 | 229,1 | 255,9 | 855 |
BWP-6/6- 3150/1250/71 | 71 | II | 9,0 | 159 | 689,1 | 956,8 | 1131,6 | 274,5 | 374,5 | 418,7 | 904 | |||||||||
BWP-6/6- 4000/1250/64 | 4000 | 64 | 1250 | I | 7,2 | 134 | 4065 | 3690 | 406 | 80 | 65 | 50 | 1 ½” | 551,7 | 765,5 | 905,3 | 222,1 | 305,9 | 343,1 | 672 |
BWP-6/6- 4000/1250/80 | 80 | II | 11,2 | 192 | 857,5 | 1190,8 | 1408,2 | 345,4 | 475,7 | 533,8 |
1030 |